OpenStudio Results

Model Summary


Information Value Units
Building Name NECB 2011-HighriseApartment-NECB HDD Method-CAN_MB_The.Pas.718670_CWEC.epw created: 2017-06-30 12:56:51 +0000 building_name
Net Site Energy 4,171,144 kBtu
Total Building Area 84,351 ft^2
EUI (Based on Net Site Energy and Total Building Area) 49.45 kBtu/ft^2
OpenStudio Standards Building Type HighriseApartment

Value
Weather File The Pas MB CAN WYEC2-B-25004 WMO#=718670
Latitude 53.97
Longitude -101.1
Elevation 889 (ft)
Time Zone -6.0
North Axis Angle 0.00
ASHRAE Climate Zone

Maximum Dry Bulb (F) Daily Temperature Range (R) Humidity Value Humidity Type Wind Speed (mph) Wind Direction
THE PAS ANN CLG .4% CONDNS DB=>MWB 83.66 18.72 66.74 Wetbulb [F] 10.74 140.0
THE PAS ANN CLG .4% CONDNS WB=>MDB 79.34 18.72 68.72 Wetbulb [F] 10.74 140.0
THE PAS ANN HTG 99.6% CONDNS DB -31.0 0.0 -31.0 Wetbulb [F] 5.82 290.0

Time Setpoint Not Met Time (hr)
During Heating 31.25
During Cooling 9.25
During Occupied Heating 31.25
During Occupied Cooling 9.25

Tolerance for Time Setpoint Not Met Temperature (F)
Heating 1.8
Cooling 1.8

Annual Overview

One or more tables in Annual Overview section returned false and was skipped.

End Use Consumption (kBtu)
Heating 2,334,256
Cooling 179,024
Interior Lighting 299,122
Exterior Lighting 0
Interior Equipment 468,544
Exterior Equipment 0
Fans 195,421
Pumps 1,526
Heat Rejection 95
Humidification 0
Heat Recovery 57
Water Systems 693,101
Refrigeration 0
Generators 0

Fuel Consumption (kBtu)
Electricity 4,171,144
Natural Gas 0
Additional Fuel 0
District Cooling 0
District Heating 0

End Use Consumption (kWh)
Heating 684,103
Cooling 52,467
Interior Lighting 87,664
Exterior Lighting 0
Interior Equipment 137,317
Exterior Equipment 0
Fans 57,272
Pumps 447
Heat Rejection 28
Humidification 0
Heat Recovery 17
Water Systems 203,128
Refrigeration 0
Generators 0

Monthly Overview


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Total
Heating 141018.33 100526.94 75451.39 46451.67 19972.28 11021.42 3868.5 6237.36 21495.28 45561.67 76671.39 135825.28 684101.5
Cooling 6.93 127.74 897.58 2044.79 7083.31 9513.03 14586.03 13457.83 3921.64 631.97 190.87 6.08 52467.8
Interior Lighting 7444.64 6725.47 7454.72 7191.47 7454.72 7211.64 7434.56 7454.72 7201.56 7444.64 7211.64 7434.56 87664.33
Exterior Lighting
Interior Equipment 11662.0 10534.06 11666.97 11279.42 11666.97 11289.33 11657.06 11666.97 11284.39 11662.0 11289.33 11657.06 137315.56
Exterior Equipment
Fans 3235.44 2973.47 3609.89 3979.83 5908.14 6690.47 8301.94 8009.39 4631.39 3493.17 3208.94 3231.39 57273.47
Pumps 18.19 19.08 33.8 40.16 49.56 49.77 49.7 53.03 44.66 43.84 28.93 16.93 447.66
Heat Rejection 0.0 0.03 0.22 0.8 3.28 4.38 7.99 7.89 2.76 0.32 0.02 0.0 27.7
Humidification
Heat Recovery 1.55 1.94 6.6 5.01 0.74 15.84
Water Systems 18338.11 16734.19 18569.64 17795.0 17839.5 16425.69 16143.36 15784.97 15310.83 16074.08 16396.83 17714.44 203126.67
Refrigeration
Generators
Total 181723.66 137640.99 117684.21 88783.13 69979.3 62207.68 62055.74 62677.18 63893.25 84911.69 114997.97 175885.73 1222440.53

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Heating 419.4178 306.0501 215.8653 163.7585 79.6477 98.6154 151.046 238.2387 360.8946
Cooling 0.0516 38.1491 43.5776 57.8165
Interior Lighting 21.5307 21.5307 21.5307 21.5307 21.5307 37.2956 37.2956 37.2956 20.7431 21.5307 21.5307 20.7431
Exterior Lighting
Interior Equipment 28.4158 28.4158 28.4158 28.4158 28.4158 31.5045 31.5045 31.5045 28.0187 28.4158 28.4158 28.0187
Exterior Equipment
Fans 4.5532 4.5532 4.5532 4.5532 4.5532 17.488 19.0293 21.9576 4.2346 4.5532 4.5532 4.2346
Pumps 0.0172 0.0172 0.0172 0.0172 0.138 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172 0.0172
Heat Rejection
Humidification
Heat Recovery 0.05 0.05
Water Systems 63.1667 56.0299 48.0741 63.1085 62.3344 57.5236 56.4515 25.9845 43.7192 59.5581 60.5609 38.1786
Refrigeration
Generators
Total 537.1 416.6 318.46 281.38 196.67 181.98 187.93 174.63 195.35 265.12 353.32 452.09

Utility Bills/Rates

No Data to Show for Utility Bills/Rates

Envelope


Construction Net Area (ft^2) Surface Count R Value (ft^2*h*R/Btu)
Customized opaque construction {1bcda80d-9ef2-454d-9a27-a1368b16f1f1} to conductance of 0.162 8,435 9 35.05
Customized opaque construction {7c847a4a-b9f3-44f4-ae0b-acd240392c20} to conductance of 0.21 31,980 140 27.04

Construction Area (ft^2) Surface Count U-Factor (Btu/ft^2*h*R)
Customized Fenestration: cond=0.220 tvis=0.220 tsol=0.232 9,516 140 0.3874

Description Total (%) North (%) East (%) South (%) West (%)
Gross Window-Wall Ratio 22.93 23.05 22.77 23.05 22.43
Gross Window-Wall Ratio (Conditioned) 22.93 23.05 22.77 23.05 22.43
Skylight-Roof Ratio 0.0

Space Type Breakdown


Space Type Name Floor Area (ft^2) Standards Building Type Standards Space Type
Space Function Corr. < 2.4m wide-sch-G 8,359 Space Function Corr. < 2.4m wide-sch-G
Space Function Dwelling Unit(s) 75,042 Space Function Dwelling Unit(s)
Space Function Office - enclosed 950 Space Function Office - enclosed

Space Type Summary


Definition Value Unit Inst. Multiplier
Space Function Corr. < 2.4m wide-sch-G People Definition 0.0009 people/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Lights Definition 0.7804 W/ft^2 1.0
Space Function Corr. < 2.4m wide-sch-G Ventilation (outdoor air method Sum) 0.0600 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Dwelling Unit(s) People Definition 0.0016 people/ft^2 1.0
Space Function Dwelling Unit(s) Elec Equip Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Lights Definition 0.4645 W/ft^2 1.0
Space Function Dwelling Unit(s) Ventilation (outdoor air method Sum) 0.0680 cfm/floor area ft^2

Definition Value Unit Inst. Multiplier
Space Function Office - enclosed People Definition 0.0046 people/ft^2 1.0
Space Function Office - enclosed Elec Equip Definition 0.6968 W/ft^2 1.0
Space Function Office - enclosed Lights Definition 1.1055 W/ft^2 1.0
Space Function Office - enclosed Ventilation (outdoor air method Sum) 0.0850 cfm/floor area ft^2

Interior Lighting Summary


Zone Lighting Power Density (W/ft^2) Total Power (W) Schedule Name Scheduled Hours/Week (hr) Actual Load Hours/Week (hr) Return Air Fraction Annual Consumption (kWh)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN SPACE FUNCTION CORR. < 2.4M WIDE-SCH-G LIGHTS SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.78 652.33 NECB-G-LIGHTING 39.2 39.2 0.0000 1333.33
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN SPACE FUNCTION DWELLING UNIT(S) LIGHTS SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 0.46 441.24 NECB-G-LIGHTING 39.2 39.2 0.0000 902.78
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN SPACE FUNCTION OFFICE - ENCLOSED LIGHTS SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 1.11 1050.15 NECB-A-LIGHTING 56.27 56.27 0.0000 3080.56

Plug Loads Summary


Electricity Annual Value (kWh)
InteriorEquipment:Electricity:Zone:SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1708.33
InteriorEquipment:Electricity:Zone:SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2450.0

Exterior Lighting

No Data to Show for Exterior Lighting

Water Use Equipment


Instance Plant Loop Definition Space Peak Flow Rate (gal/min) Flow Rate Schedule Target Temp Range (F)
F2 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n1 apartment Service Water Use Def 0.06gal/min F2 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 n2 apartment Service Water Use Def 0.06gal/min F2 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F2 ne apartment Service Water Use Def 0.06gal/min F2 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 nw apartment Service Water Use Def 0.06gal/min F2 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s1 apartment Service Water Use Def 0.06gal/min F2 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F2 s2 apartment Service Water Use Def 0.06gal/min F2 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 se apartment Service Water Use 0.06gal/min Main Service Water Loop F2 se apartment Service Water Use Def 0.06gal/min F2 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F2 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F2 sw apartment Service Water Use Def 0.06gal/min F2 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n1 apartment Service Water Use Def 0.06gal/min F3 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 n2 apartment Service Water Use Def 0.06gal/min F3 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F3 ne apartment Service Water Use Def 0.06gal/min F3 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 nw apartment Service Water Use Def 0.06gal/min F3 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s1 apartment Service Water Use Def 0.06gal/min F3 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F3 s2 apartment Service Water Use Def 0.06gal/min F3 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 se apartment Service Water Use 0.06gal/min Main Service Water Loop F3 se apartment Service Water Use Def 0.06gal/min F3 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F3 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F3 sw apartment Service Water Use Def 0.06gal/min F3 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n1 apartment Service Water Use Def 0.06gal/min F4 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 n2 apartment Service Water Use Def 0.06gal/min F4 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F4 ne apartment Service Water Use Def 0.06gal/min F4 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 nw apartment Service Water Use Def 0.06gal/min F4 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s1 apartment Service Water Use Def 0.06gal/min F4 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F4 s2 apartment Service Water Use Def 0.06gal/min F4 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 se apartment Service Water Use 0.06gal/min Main Service Water Loop F4 se apartment Service Water Use Def 0.06gal/min F4 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F4 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F4 sw apartment Service Water Use Def 0.06gal/min F4 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n1 apartment Service Water Use Def 0.06gal/min F6 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 n2 apartment Service Water Use Def 0.06gal/min F6 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F6 ne apartment Service Water Use Def 0.06gal/min F6 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 nw apartment Service Water Use Def 0.06gal/min F6 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s1 apartment Service Water Use Def 0.06gal/min F6 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F6 s2 apartment Service Water Use Def 0.06gal/min F6 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 se apartment Service Water Use 0.06gal/min Main Service Water Loop F6 se apartment Service Water Use Def 0.06gal/min F6 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F6 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F6 sw apartment Service Water Use Def 0.06gal/min F6 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n1 apartment Service Water Use Def 0.06gal/min F7 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 n2 apartment Service Water Use Def 0.06gal/min F7 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F7 ne apartment Service Water Use Def 0.06gal/min F7 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 nw apartment Service Water Use Def 0.06gal/min F7 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s1 apartment Service Water Use Def 0.06gal/min F7 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F7 s2 apartment Service Water Use Def 0.06gal/min F7 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 se apartment Service Water Use 0.06gal/min Main Service Water Loop F7 se apartment Service Water Use Def 0.06gal/min F7 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F7 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F7 sw apartment Service Water Use Def 0.06gal/min F7 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n1 apartment Service Water Use Def 0.06gal/min F8 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 n2 apartment Service Water Use Def 0.06gal/min F8 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F8 ne apartment Service Water Use Def 0.06gal/min F8 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 nw apartment Service Water Use Def 0.06gal/min F8 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s1 apartment Service Water Use Def 0.06gal/min F8 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F8 s2 apartment Service Water Use Def 0.06gal/min F8 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 se apartment Service Water Use 0.06gal/min Main Service Water Loop F8 se apartment Service Water Use Def 0.06gal/min F8 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F8 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F8 sw apartment Service Water Use Def 0.06gal/min F8 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n1 apartment Service Water Use Def 0.06gal/min F9 N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 n2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 n2 apartment Service Water Use Def 0.06gal/min F9 N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 ne apartment Service Water Use 0.06gal/min Main Service Water Loop F9 ne apartment Service Water Use Def 0.06gal/min F9 NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 nw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 nw apartment Service Water Use Def 0.06gal/min F9 NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s1 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s1 apartment Service Water Use Def 0.06gal/min F9 S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 s2 apartment Service Water Use 0.06gal/min Main Service Water Loop F9 s2 apartment Service Water Use Def 0.06gal/min F9 S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 se apartment Service Water Use 0.06gal/min Main Service Water Loop F9 se apartment Service Water Use Def 0.06gal/min F9 SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
F9 sw apartment Service Water Use 0.06gal/min Main Service Water Loop F9 sw apartment Service Water Use Def 0.06gal/min F9 SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n1 apartment Service Water Use 0.06gal/min Main Service Water Loop G n1 apartment Service Water Use Def 0.06gal/min G N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G n2 apartment Service Water Use 0.06gal/min Main Service Water Loop G n2 apartment Service Water Use Def 0.06gal/min G N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G ne apartment Service Water Use 0.06gal/min Main Service Water Loop G ne apartment Service Water Use Def 0.06gal/min G NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G nw apartment Service Water Use 0.06gal/min Main Service Water Loop G nw apartment Service Water Use Def 0.06gal/min G NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s1 apartment Service Water Use 0.06gal/min Main Service Water Loop G s1 apartment Service Water Use Def 0.06gal/min G S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G s2 apartment Service Water Use 0.06gal/min Main Service Water Loop G s2 apartment Service Water Use Def 0.06gal/min G S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
G sw apartment Service Water Use 0.06gal/min Main Service Water Loop G sw apartment Service Water Use Def 0.06gal/min G SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n1 apartment Service Water Use 0.06gal/min Main Service Water Loop M n1 apartment Service Water Use Def 0.06gal/min M N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M n2 apartment Service Water Use 0.06gal/min Main Service Water Loop M n2 apartment Service Water Use Def 0.06gal/min M N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M ne apartment Service Water Use 0.06gal/min Main Service Water Loop M ne apartment Service Water Use Def 0.06gal/min M NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M nw apartment Service Water Use 0.06gal/min Main Service Water Loop M nw apartment Service Water Use Def 0.06gal/min M NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s1 apartment Service Water Use 0.06gal/min Main Service Water Loop M s1 apartment Service Water Use Def 0.06gal/min M S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M s2 apartment Service Water Use 0.06gal/min Main Service Water Loop M s2 apartment Service Water Use Def 0.06gal/min M S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M se apartment Service Water Use 0.06gal/min Main Service Water Loop M se apartment Service Water Use Def 0.06gal/min M SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
M sw apartment Service Water Use 0.06gal/min Main Service Water Loop M sw apartment Service Water Use Def 0.06gal/min M SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
Office Service Water Use 0.03gal/min Main Service Water Loop Office Service Water Use Def 0.03gal/min Office 0.03 NECB-A-Service Water Heating 140.0 to 140.0
T n1 apartment Service Water Use 0.06gal/min Main Service Water Loop T n1 apartment Service Water Use Def 0.06gal/min T N1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T n2 apartment Service Water Use 0.06gal/min Main Service Water Loop T n2 apartment Service Water Use Def 0.06gal/min T N2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T ne apartment Service Water Use 0.06gal/min Main Service Water Loop T ne apartment Service Water Use Def 0.06gal/min T NE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T nw apartment Service Water Use 0.06gal/min Main Service Water Loop T nw apartment Service Water Use Def 0.06gal/min T NW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s1 apartment Service Water Use 0.06gal/min Main Service Water Loop T s1 apartment Service Water Use Def 0.06gal/min T S1 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T s2 apartment Service Water Use 0.06gal/min Main Service Water Loop T s2 apartment Service Water Use Def 0.06gal/min T S2 Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T se apartment Service Water Use 0.06gal/min Main Service Water Loop T se apartment Service Water Use Def 0.06gal/min T SE Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0
T sw apartment Service Water Use 0.06gal/min Main Service Water Loop T sw apartment Service Water Use Def 0.06gal/min T SW Apartment 0.06 NECB-G-Service Water Heating 140.0 to 140.0

HVAC Load Profiles


Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Average Outdoor Air Dry Bulb (F) -2.9 3.5 16.6 31.7 51.3 58.4 65.4 63.7 49.6 37.1 20.8 0.7
Cooling Load (MBtu) 0.02 0.44 3.06 6.98 24.17 32.46 49.77 45.92 13.38 2.16 0.65 0.02
Heating Load (MBtu) 481.17 343.01 257.45 158.5 68.15 37.61 13.2 21.28 73.34 155.46 261.61 463.46

Zone Conditions


Zone Unmet Htg (hr) Unmet Htg - Occ (hr) < 56 (F) 56-61 (F) 61-66 (F) 66-68 (F) 68-70 (F) 70-72 (F) 72-74 (F) 74-76 (F) 76-78 (F) 78-83 (F) 83-88 (F) >= 88 (F) Unmet Clg (hr) Unmet Clg - Occ (hr) Mean Temp (F)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 74 597 2599 1193 4297 0 0 0 0 0 0 73.2 (F)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 69 360 648 3213 869 3601 0 0 0 0 0 0 72.6 (F)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 69 361 650 3216 858 3606 0 0 0 0 0 0 72.6 (F)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 386 463 399 3355 688 3469 0 0 0 0 0 0 72.3 (F)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 0 0 0 0 378 456 413 3336 724 3453 0 0 0 0 0 0 72.3 (F)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 20 165 498 1920 950 5207 0 0 0 0 0 0 73.4 (F)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 20 170 495 1913 943 5219 0 0 0 0 0 0 73.4 (F)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 253 357 316 2357 800 4676 1 0 0 0 0 0 73.0 (F)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 225 369 343 2419 824 4580 0 0 0 0 0 0 73.0 (F)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 68 586 2553 1181 4372 0 0 0 0 0 0 73.2 (F)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 82 353 638 3193 828 3666 0 0 0 0 0 0 72.6 (F)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 82 354 643 3190 818 3673 0 0 0 0 0 0 72.6 (F)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 396 458 394 3331 672 3509 0 0 0 0 0 0 72.3 (F)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 0 0 0 0 391 447 409 3323 686 3504 0 0 0 0 0 0 72.3 (F)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 23 173 478 1920 887 5279 0 0 0 0 0 0 73.5 (F)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 24 174 477 1917 889 5279 0 0 0 0 0 0 73.5 (F)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 245 358 329 2379 798 4651 0 0 0 0 0 0 73.0 (F)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 239 359 338 2404 799 4621 0 0 0 0 0 0 73.0 (F)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 76 590 2555 1162 4377 0 0 0 0 0 0 73.2 (F)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 89 361 633 3195 818 3664 0 0 0 0 0 0 72.6 (F)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 89 363 634 3197 805 3672 0 0 0 0 0 0 72.6 (F)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 411 462 380 3346 673 3488 0 0 0 0 0 0 72.3 (F)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 0 0 0 0 401 447 401 3342 685 3484 0 0 0 0 0 0 72.3 (F)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 37 168 487 1940 870 5258 0 0 0 0 0 0 73.4 (F)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 37 168 486 1938 872 5259 0 0 0 0 0 0 73.4 (F)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 256 371 317 2405 813 4598 0 0 0 0 0 0 73.0 (F)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 256 360 327 2414 803 4600 0 0 0 0 0 0 73.0 (F)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 90 603 2601 1164 4302 0 0 0 0 0 0 73.2 (F)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 105 361 643 3237 837 3577 0 0 0 0 0 0 72.6 (F)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 105 364 640 3242 818 3591 0 0 0 0 0 0 72.6 (F)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 434 468 374 3390 678 3416 0 0 0 0 0 0 72.3 (F)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 0 0 0 0 428 455 384 3406 665 3421 1 0 0 0 0 0 72.3 (F)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 51 182 490 2016 842 5179 0 0 0 0 0 0 73.4 (F)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 51 182 490 2017 840 5180 0 0 0 0 0 0 73.4 (F)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 271 387 319 2462 819 4502 0 0 0 0 0 0 72.9 (F)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 273 380 317 2478 807 4505 0 0 0 0 0 0 72.9 (F)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 98 612 2660 1171 4219 0 0 0 0 0 0 73.1 (F)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 119 369 635 3274 852 3511 0 0 0 0 0 0 72.5 (F)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 119 371 636 3274 846 3514 0 0 0 0 0 0 72.5 (F)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 444 473 374 3436 677 3356 0 0 0 0 0 0 72.2 (F)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 0 0 0 0 437 467 381 3450 652 3372 1 0 0 0 0 0 72.2 (F)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 58 189 498 2064 853 5098 0 0 0 0 0 0 73.3 (F)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 58 189 499 2066 853 5095 0 0 0 0 0 0 73.3 (F)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 282 396 325 2488 836 4433 0 0 0 0 0 0 72.9 (F)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 282 387 323 2521 802 4445 0 0 0 0 0 0 72.9 (F)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 112 630 2761 1198 4059 0 0 0 0 0 0 73.1 (F)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 136 393 624 3366 859 3382 0 0 0 0 0 0 72.5 (F)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 136 393 626 3365 860 3380 0 0 0 0 0 0 72.5 (F)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 464 479 372 3502 683 3260 0 0 0 0 0 0 72.2 (F)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 0 0 0 0 452 473 382 3534 617 3301 1 0 0 0 0 0 72.2 (F)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 64 205 512 2157 879 4943 0 0 0 0 0 0 73.3 (F)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 64 205 517 2151 882 4941 0 0 0 0 0 0 73.3 (F)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 306 404 328 2563 849 4310 0 0 0 0 0 0 72.8 (F)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 301 398 330 2583 821 4327 0 0 0 0 0 0 72.8 (F)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0 0 0 0 4 188 658 3014 1163 3733 0 0 0 0 0 0 72.9 (F)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 197 457 569 3604 781 3152 0 0 0 0 0 0 72.3 (F)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 198 458 569 3605 779 3151 0 0 0 0 0 0 72.3 (F)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 555 444 382 3633 675 3071 0 0 0 0 0 0 72.0 (F)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 0 0 0 0 537 449 388 3637 651 3097 1 0 0 0 0 0 72.1 (F)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 103 280 503 2367 963 4544 0 0 0 0 0 0 73.1 (F)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 103 282 501 2369 961 4544 0 0 0 0 0 0 73.1 (F)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 378 408 347 2758 848 4021 0 0 0 0 0 0 72.6 (F)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 379 396 344 2775 834 4031 1 0 0 0 0 0 72.6 (F)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0 0 0 0 4 232 612 2696 1340 3876 0 0 0 0 0 0 72.9 (F)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 99 411 641 3319 973 3317 0 0 0 0 0 0 72.5 (F)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 100 414 640 3319 974 3313 0 0 0 0 0 0 72.5 (F)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 435 474 380 3443 777 3251 0 0 0 0 0 0 72.2 (F)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 0 0 0 0 421 481 379 3458 772 3249 0 0 0 0 0 0 72.2 (F)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 34 232 522 2041 1094 4836 1 0 0 0 0 0 73.3 (F)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 35 249 509 2014 1083 4866 4 0 0 0 0 0 73.3 (F)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 289 384 367 2469 964 4285 2 0 0 0 0 0 72.8 (F)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0 0 0 0 0 84 591 2578 1158 4349 0 0 0 0 0 0 73.2 (F)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 97 362 629 3213 830 3629 0 0 0 0 0 0 72.6 (F)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 98 361 634 3217 809 3641 0 0 0 0 0 0 72.6 (F)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 421 467 375 3373 675 3449 0 0 0 0 0 0 72.3 (F)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 0 0 0 0 416 446 401 3367 675 3454 1 0 0 0 0 0 72.3 (F)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 44 178 486 1971 850 5231 0 0 0 0 0 0 73.4 (F)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 44 179 485 1971 857 5224 0 0 0 0 0 0 73.4 (F)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 266 377 321 2427 824 4545 0 0 0 0 0 0 72.9 (F)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 0 0 0 0 265 371 318 2451 801 4554 0 0 0 0 0 0 72.9 (F)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 0 0 0 0 781 562 509 1640 952 2709 789 689 129 0 9 9 73.1 (F)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 1 1 0 0 727 385 438 3536 930 2744 0 0 0 0 0 0 71.8 (F)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 30 30 0 0 976 398 322 3957 748 2359 0 0 0 0 0 0 71.5 (F)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 31 31 0 0 978 397 322 3959 750 2354 0 0 0 0 0 0 71.5 (F)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 30 30 0 0 1133 300 330 3927 689 2381 0 0 0 0 0 0 71.4 (F)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 28 28 0 0 1125 295 334 3922 681 2399 4 0 0 0 0 0 71.4 (F)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 12 12 0 0 814 394 346 3146 904 3156 0 0 0 0 0 0 71.9 (F)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 12 12 0 0 815 394 348 3150 907 3146 0 0 0 0 0 0 71.9 (F)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 13 13 0 0 1018 300 340 3312 762 3028 0 0 0 0 0 0 71.8 (F)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 13 13 0 0 1017 289 355 3306 787 3001 5 0 0 0 0 0 71.7 (F)

Zone < 30 (%) 30-35 (%) 35-40 (%) 40-45 (%) 45-50 (%) 50-55 (%) 55-60 (%) 60-65 (%) 65-70 (%) 70-75 (%) 75-80 (%) >= 80 (%) Mean Relative Humidity (%)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 6204 505 626 698 479 203 43 2 0 0 0 0 21.7 (%)
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4699 976 765 610 717 590 285 107 11 0 0 0 30.5 (%)
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4698 975 770 605 721 594 281 105 11 0 0 0 30.5 (%)
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4745 965 767 712 773 517 204 77 0 0 0 0 29.9 (%)
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 4771 930 784 693 786 498 232 66 0 0 0 0 29.9 (%)
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5012 874 723 676 742 460 220 52 1 0 0 0 29.2 (%)
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5011 880 721 680 741 463 212 52 0 0 0 0 29.2 (%)
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5022 871 765 810 769 364 140 19 0 0 0 0 28.8 (%)
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 5008 870 759 773 756 385 173 36 0 0 0 0 28.9 (%)
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 6207 508 630 695 478 200 40 2 0 0 0 0 21.7 (%)
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4749 966 751 624 710 579 272 100 9 0 0 0 30.2 (%)
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4747 967 752 622 711 585 266 101 9 0 0 0 30.2 (%)
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4823 929 759 708 766 502 202 71 0 0 0 0 29.6 (%)
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 4834 914 768 697 785 483 223 56 0 0 0 0 29.6 (%)
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5048 867 716 680 737 453 211 48 0 0 0 0 29.0 (%)
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5049 866 717 680 733 459 209 47 0 0 0 0 29.0 (%)
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5055 855 754 769 748 398 152 29 0 0 0 0 28.7 (%)
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 5056 859 746 774 747 378 168 32 0 0 0 0 28.7 (%)
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 6208 506 631 695 478 198 42 2 0 0 0 0 21.7 (%)
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4776 949 750 624 705 577 270 99 10 0 0 0 30.2 (%)
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4774 951 748 623 708 578 267 102 9 0 0 0 30.2 (%)
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4850 920 753 702 765 498 199 73 0 0 0 0 29.5 (%)
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 4870 895 773 681 782 476 226 57 0 0 0 0 29.5 (%)
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5068 859 712 679 731 452 211 48 0 0 0 0 29.0 (%)
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5066 856 714 681 728 457 210 47 1 0 0 0 29.0 (%)
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5076 844 747 761 734 407 158 33 0 0 0 0 28.6 (%)
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 5089 842 740 763 747 376 170 33 0 0 0 0 28.6 (%)
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 6208 504 630 693 479 200 44 2 0 0 0 0 21.7 (%)
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4787 947 743 620 701 580 270 102 10 0 0 0 30.1 (%)
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4788 942 748 615 708 577 269 102 11 0 0 0 30.1 (%)
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4878 911 748 690 760 493 200 78 2 0 0 0 29.4 (%)
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 4896 883 761 684 774 473 227 62 0 0 0 0 29.4 (%)
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5084 850 706 675 730 452 213 49 1 0 0 0 28.9 (%)
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5082 851 704 681 726 453 211 51 1 0 0 0 28.9 (%)
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5097 840 727 760 730 406 162 38 0 0 0 0 28.5 (%)
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 5109 832 736 756 739 376 175 37 0 0 0 0 28.5 (%)
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 6204 505 630 692 482 201 44 2 0 0 0 0 21.7 (%)
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4780 946 745 617 708 578 273 102 11 0 0 0 30.1 (%)
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4775 950 748 616 709 580 269 102 11 0 0 0 30.1 (%)
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4891 893 750 690 755 498 201 79 3 0 0 0 29.3 (%)
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 4905 871 762 686 769 475 230 62 0 0 0 0 29.3 (%)
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5079 855 706 672 730 453 213 51 1 0 0 0 28.9 (%)
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5077 853 706 675 728 454 215 50 2 0 0 0 28.9 (%)
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5104 837 723 758 727 405 167 39 0 0 0 0 28.5 (%)
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 5117 824 733 756 740 375 178 37 0 0 0 0 28.5 (%)
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 6196 506 632 693 486 199 46 2 0 0 0 0 21.7 (%)
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4751 952 751 616 712 586 276 104 12 0 0 0 30.1 (%)
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4750 955 750 620 707 589 274 104 11 0 0 0 30.1 (%)
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4879 891 746 701 754 502 203 81 3 0 0 0 29.3 (%)
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 4901 862 759 684 778 477 232 67 0 0 0 0 29.3 (%)
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5063 858 710 674 731 454 217 50 3 0 0 0 28.9 (%)
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5062 855 711 676 729 456 217 51 3 0 0 0 28.9 (%)
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5102 829 727 754 731 401 175 41 0 0 0 0 28.5 (%)
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 5108 827 731 755 742 379 179 39 0 0 0 0 28.5 (%)
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 6168 508 629 702 487 212 52 2 0 0 0 0 21.9 (%)
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4699 944 759 623 727 595 291 111 11 0 0 0 30.3 (%)
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4698 947 754 625 719 607 288 111 11 0 0 0 30.3 (%)
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4845 886 752 692 772 515 212 80 6 0 0 0 29.5 (%)
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 4860 869 761 682 784 478 251 73 2 0 0 0 29.5 (%)
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4996 887 702 685 740 458 229 60 3 0 0 0 29.1 (%)
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 4993 886 703 688 736 461 230 60 3 0 0 0 29.2 (%)
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5061 832 732 761 736 410 178 49 1 0 0 0 28.6 (%)
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 5069 834 729 757 747 383 192 49 0 0 0 0 28.6 (%)
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 6167 512 603 672 507 213 78 8 0 0 0 0 22.0 (%)
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4555 991 766 604 685 642 328 153 36 0 0 0 31.2 (%)
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4556 989 769 605 682 640 331 150 38 0 0 0 31.2 (%)
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4602 973 801 685 753 568 263 92 23 0 0 0 30.6 (%)
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 4623 965 791 657 783 542 289 93 17 0 0 0 30.6 (%)
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4880 909 714 648 695 547 260 97 10 0 0 0 29.9 (%)
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4889 912 709 665 706 538 246 87 8 0 0 0 29.8 (%)
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 4880 916 745 734 739 449 221 73 3 0 0 0 29.6 (%)
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 6209 504 630 694 479 199 43 2 0 0 0 0 21.7 (%)
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4780 950 745 624 703 576 270 102 10 0 0 0 30.1 (%)
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4781 948 747 621 705 580 265 103 10 0 0 0 30.1 (%)
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4864 919 750 694 763 495 200 75 0 0 0 0 29.4 (%)
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 4884 896 762 681 780 471 226 60 0 0 0 0 29.4 (%)
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5080 852 709 676 729 454 212 47 1 0 0 0 28.9 (%)
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5076 853 708 682 726 454 210 50 1 0 0 0 28.9 (%)
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5089 840 739 758 733 406 160 35 0 0 0 0 28.6 (%)
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 5103 835 736 758 745 376 173 34 0 0 0 0 28.5 (%)
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 3598 1181 1311 1453 1059 139 19 0 0 0 0 0 32.8 (%)
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 6056 537 555 657 489 275 137 45 8 1 0 0 22.3 (%)
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4991 792 701 586 639 537 318 138 50 8 0 0 29.0 (%)
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 4994 793 706 597 641 535 305 133 49 7 0 0 28.9 (%)
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5046 795 709 623 666 472 272 126 45 6 0 0 28.4 (%)
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 5073 770 694 639 660 467 292 116 44 5 0 0 28.4 (%)
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5148 788 640 623 642 498 270 114 33 4 0 0 28.3 (%)
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5147 787 637 632 636 500 269 113 35 4 0 0 28.3 (%)
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5165 770 691 664 636 459 238 100 32 5 0 0 27.9 (%)
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 5195 757 654 690 629 454 245 99 33 4 0 0 27.9 (%)

Zone Overview


Area (ft^2) Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume (ft^3) Multiplier Above Ground Gross Wall Area (ft^2) Underground Gross Wall Area (ft^2) Window Glass Area (ft^2) Lighting (W/ft^2) People (ft^2/person) Plug and Process (W/ft^2)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 37.03 0.78 1075.31 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 1.11 215.06 0.7
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 835.93 Yes Yes 8358.63 1.00 110.01 0.0 18.41 0.78 1075.31 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.59 1.00 379.97 0.0 87.62 0.46 645.19 0.46
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 949.92 Yes Yes 9498.23 1.00 629.9 0.0 145.21 0.46 645.19 0.46
Total 84351.17 843456.88 41495.09 0.0 9515.51 0.5 656.38 0.42
Conditioned Total 84351.17 843456.88 41495.09 0.0 9515.51 0.5 656.38 0.42
Unconditioned Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Not Part of Total 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Heating/Cooling Calculated Design Load Design Load With Sizing Factor Calculated Design Air Flow (ft^3/min) Design Air Flow With Sizing Factor (ft^3/min) Date/Time Of Peak Outdoor Temperature at Peak Load (F) Outdoor Humidity Ratio at Peak Load (lbWater/lbAir)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 216.13 7/21 20:30:00 73.45 0.01
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN Heating 5.46 (kBtu/h) 7.1 (kBtu/h) 133.49 173.75 1/21 09:00:00 -31.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 163.15 180.1 7/21 20:15:00 73.89 0.01
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.52 (kBtu/h) 7.18 (kBtu/h) 137.73 177.99 1/21 09:30:00 -31.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.28 (ton) 0.31 (ton) 161.03 175.87 7/21 20:15:00 73.89 0.01
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 5.52 (kBtu/h) 7.18 (kBtu/h) 137.73 177.99 1/21 09:30:00 -31.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.5 (ton) 260.62 286.05 7/21 09:00:00 73.36 0.01
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.32 (kBtu/h) 10.81 (kBtu/h) 207.65 269.1 1/21 09:30:00 -31.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Cooling 0.52 (ton) 0.57 (ton) 296.64 326.31 7/21 20:00:00 74.3 0.01
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN Heating 8.37 (kBtu/h) 10.88 (kBtu/h) 207.65 271.22 1/21 09:30:00 -31.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.44 (ton) 0.48 (ton) 250.03 275.45 7/21 14:00:00 83.66 0.01
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.43 (kBtu/h) 7.06 (kBtu/h) 135.61 175.87 1/21 09:30:00 -31.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 5.44 (kBtu/h) 7.07 (kBtu/h) 135.61 175.87 1/21 09:30:00 -31.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.62 (ton) 0.68 (ton) 353.85 389.87 7/21 14:00:00 83.66 0.01
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.28 (kBtu/h) 10.76 (kBtu/h) 205.53 266.98 1/21 09:30:00 -31.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Cooling 0.62 (ton) 0.69 (ton) 355.97 391.99 7/21 19:00:00 76.35 0.01
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN Heating 8.29 (kBtu/h) 10.78 (kBtu/h) 205.53 266.98 1/21 09:30:00 -31.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN Heating 5.39 (kBtu/h) 7.01 (kBtu/h) 131.37 171.63 1/21 09:00:00 -31.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.59 (kBtu/h) 7.27 (kBtu/h) 139.85 180.1 1/21 09:30:00 -31.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 163.15 180.1 7/21 20:15:00 73.89 0.01
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 5.59 (kBtu/h) 7.27 (kBtu/h) 139.85 180.1 1/21 09:30:00 -31.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 290.29 7/21 09:00:00 73.36 0.01
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.45 (kBtu/h) 10.98 (kBtu/h) 209.77 273.34 1/21 09:30:00 -31.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 298.76 328.43 7/21 20:00:00 74.3 0.01
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN Heating 8.5 (kBtu/h) 11.05 (kBtu/h) 211.89 275.45 1/21 09:30:00 -31.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.5 (kBtu/h) 7.15 (kBtu/h) 137.73 177.99 1/21 09:30:00 -31.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 256.38 281.81 7/21 14:00:00 83.66 0.01
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 5.5 (kBtu/h) 7.15 (kBtu/h) 137.73 177.99 1/21 09:30:00 -31.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.38 (kBtu/h) 10.89 (kBtu/h) 207.65 271.22 1/21 09:30:00 -31.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN Heating 8.42 (kBtu/h) 10.95 (kBtu/h) 209.77 271.22 1/21 09:30:00 -31.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN Heating 5.43 (kBtu/h) 7.06 (kBtu/h) 131.37 171.63 1/21 09:00:00 -31.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.68 (kBtu/h) 7.39 (kBtu/h) 141.96 184.34 1/21 09:30:00 -31.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 180.1 7/21 20:15:00 73.89 0.01
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 5.68 (kBtu/h) 7.38 (kBtu/h) 141.96 184.34 1/21 09:30:00 -31.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 290.29 7/21 09:00:00 73.36 0.01
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.58 (kBtu/h) 11.15 (kBtu/h) 214.01 277.57 1/21 09:30:00 -31.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 300.88 330.55 7/21 20:00:00 74.3 0.01
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN Heating 8.64 (kBtu/h) 11.23 (kBtu/h) 214.01 279.69 1/21 09:30:00 -31.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.59 (kBtu/h) 7.26 (kBtu/h) 139.85 180.1 1/21 09:30:00 -31.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 256.38 281.81 7/21 14:00:00 83.66 0.01
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 5.58 (kBtu/h) 7.26 (kBtu/h) 139.85 180.1 1/21 09:30:00 -31.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.49 (kBtu/h) 11.04 (kBtu/h) 211.89 275.45 1/21 09:30:00 -31.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN Heating 8.55 (kBtu/h) 11.11 (kBtu/h) 211.89 275.45 1/21 09:30:00 -31.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN Heating 5.51 (kBtu/h) 7.17 (kBtu/h) 133.49 173.75 1/21 09:00:00 -31.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.83 (kBtu/h) 7.58 (kBtu/h) 144.08 188.58 1/21 09:30:00 -31.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 180.1 7/21 20:15:00 73.89 0.01
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 5.83 (kBtu/h) 7.57 (kBtu/h) 144.08 188.58 1/21 09:30:00 -31.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 290.29 7/21 09:00:00 73.36 0.01
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.79 (kBtu/h) 11.42 (kBtu/h) 218.24 283.93 1/21 09:30:00 -31.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 298.76 330.55 7/21 20:00:00 74.3 0.01
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN Heating 8.85 (kBtu/h) 11.5 (kBtu/h) 220.36 286.05 1/21 09:30:00 -31.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.73 (kBtu/h) 7.45 (kBtu/h) 141.96 184.34 1/21 09:30:00 -31.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 256.38 283.93 7/21 14:00:00 83.66 0.01
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 5.73 (kBtu/h) 7.45 (kBtu/h) 141.96 184.34 1/21 09:30:00 -31.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.7 (kBtu/h) 11.3 (kBtu/h) 216.13 281.81 1/21 09:30:00 -31.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN Heating 8.75 (kBtu/h) 11.38 (kBtu/h) 218.24 283.93 1/21 09:30:00 -31.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN Heating 5.56 (kBtu/h) 7.23 (kBtu/h) 135.61 175.87 1/21 09:00:00 -31.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.9 (kBtu/h) 7.67 (kBtu/h) 146.2 190.7 1/21 09:30:00 -31.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 180.1 7/21 20:15:00 73.89 0.01
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 5.9 (kBtu/h) 7.67 (kBtu/h) 146.2 190.7 1/21 09:30:00 -31.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 288.17 7/21 09:00:00 73.36 0.01
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 8.88 (kBtu/h) 11.55 (kBtu/h) 220.36 288.17 1/21 09:30:00 -31.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 298.76 330.55 7/21 20:00:00 74.3 0.01
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN Heating 8.94 (kBtu/h) 11.63 (kBtu/h) 222.48 288.17 1/21 09:30:00 -31.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.8 (kBtu/h) 7.54 (kBtu/h) 144.08 188.58 1/21 09:30:00 -31.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 256.38 283.93 7/21 14:00:00 83.66 0.01
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 5.8 (kBtu/h) 7.54 (kBtu/h) 144.08 186.46 1/21 09:30:00 -31.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 8.79 (kBtu/h) 11.43 (kBtu/h) 218.24 283.93 1/21 09:30:00 -31.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN Heating 8.85 (kBtu/h) 11.51 (kBtu/h) 220.36 286.05 1/21 09:30:00 -31.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN Heating 5.71 (kBtu/h) 7.43 (kBtu/h) 139.85 180.1 1/21 09:00:00 -31.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.04 (kBtu/h) 7.86 (kBtu/h) 150.44 194.94 1/21 09:30:00 -31.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 182.22 7/21 20:15:00 73.89 0.01
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 6.04 (kBtu/h) 7.85 (kBtu/h) 150.44 194.94 1/21 09:30:00 -31.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 288.17 7/21 09:00:00 73.36 0.01
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 9.05 (kBtu/h) 11.76 (kBtu/h) 224.6 292.41 1/21 09:30:00 -31.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 300.88 330.55 7/21 20:00:00 74.3 0.01
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN Heating 9.11 (kBtu/h) 11.84 (kBtu/h) 226.72 294.52 1/21 09:30:00 -31.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 5.95 (kBtu/h) 7.73 (kBtu/h) 148.32 192.82 1/21 09:30:00 -31.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 256.38 281.81 7/21 14:00:00 83.66 0.01
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 5.94 (kBtu/h) 7.73 (kBtu/h) 148.32 192.82 1/21 09:30:00 -31.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 8.95 (kBtu/h) 11.64 (kBtu/h) 222.48 290.29 1/21 09:30:00 -31.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN Heating 9.01 (kBtu/h) 11.72 (kBtu/h) 224.6 292.41 1/21 09:30:00 -31.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Cooling 0.36 (ton) 0.39 (ton) 203.41 222.48 7/21 20:30:00 73.45 0.01
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN Heating 6.63 (kBtu/h) 8.62 (kBtu/h) 161.03 209.77 1/21 09:00:00 -31.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.31 (ton) 0.34 (ton) 173.75 190.7 7/21 20:15:00 73.89 0.01
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.72 (kBtu/h) 8.74 (kBtu/h) 167.39 218.24 1/21 09:30:00 -31.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.3 (ton) 0.33 (ton) 169.51 186.46 7/21 20:15:00 73.89 0.01
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 6.72 (kBtu/h) 8.74 (kBtu/h) 167.39 218.24 1/21 09:30:00 -31.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.5 (ton) 260.62 286.05 7/21 09:00:00 73.36 0.01
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.74 (kBtu/h) 12.67 (kBtu/h) 241.55 315.71 1/21 09:30:00 -31.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Cooling 0.54 (ton) 0.59 (ton) 307.24 339.02 7/21 20:00:00 74.3 0.01
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN Heating 9.8 (kBtu/h) 12.75 (kBtu/h) 243.67 317.83 1/21 09:30:00 -31.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.46 (ton) 0.5 (ton) 258.5 283.93 7/21 14:15:00 83.66 0.01
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.63 (kBtu/h) 8.61 (kBtu/h) 165.27 214.01 1/21 09:30:00 -31.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.46 (ton) 0.51 (ton) 260.62 288.17 7/21 14:15:00 83.66 0.01
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 6.62 (kBtu/h) 8.61 (kBtu/h) 165.27 214.01 1/21 09:30:00 -31.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.61 (ton) 0.67 (ton) 347.5 383.52 7/21 14:00:00 83.66 0.01
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.65 (kBtu/h) 12.54 (kBtu/h) 239.43 311.48 1/21 09:30:00 -31.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Cooling 0.64 (ton) 0.71 (ton) 366.57 402.59 7/21 19:00:00 76.35 0.01
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN Heating 9.71 (kBtu/h) 12.62 (kBtu/h) 241.55 313.59 1/21 09:30:00 -31.0 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Cooling 0.31 (ton) 0.34 (ton) 177.99 197.06 7/21 09:00:00 73.36 0.01
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN Heating 6.06 (kBtu/h) 7.88 (kBtu/h) 148.32 192.82 1/21 09:00:00 -31.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.26 (ton) 0.29 (ton) 148.32 163.15 7/21 20:15:00 73.89 0.01
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.37 (kBtu/h) 6.98 (kBtu/h) 133.49 173.75 1/21 09:30:00 -31.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.25 (ton) 0.28 (ton) 144.08 158.92 7/21 20:15:00 73.89 0.01
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 5.37 (kBtu/h) 6.98 (kBtu/h) 133.49 173.75 1/21 09:30:00 -31.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.48 (ton) 0.53 (ton) 273.34 300.88 7/21 09:00:00 73.36 0.01
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 7.97 (kBtu/h) 10.36 (kBtu/h) 194.94 252.15 1/21 09:00:00 -31.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Cooling 0.51 (ton) 0.56 (ton) 288.17 317.83 7/21 19:00:00 76.35 0.01
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN Heating 8.02 (kBtu/h) 10.42 (kBtu/h) 194.94 254.27 1/21 09:00:00 -31.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 258.5 283.93 7/21 13:45:00 83.43 0.01
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.3 (kBtu/h) 6.89 (kBtu/h) 131.37 171.63 1/21 09:30:00 -31.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.47 (ton) 0.51 (ton) 264.86 292.41 7/21 13:45:00 83.43 0.01
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 5.25 (kBtu/h) 6.82 (kBtu/h) 131.37 169.51 1/21 09:30:00 -31.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Cooling 0.61 (ton) 0.67 (ton) 345.38 379.28 7/21 17:00:00 81.03 0.01
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN Heating 7.95 (kBtu/h) 10.33 (kBtu/h) 194.94 252.15 1/21 09:00:00 -31.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Cooling 0.35 (ton) 0.38 (ton) 197.06 218.24 7/21 20:30:00 73.45 0.01
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN Heating 5.47 (kBtu/h) 7.12 (kBtu/h) 133.49 173.75 1/21 09:00:00 -31.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 167.39 184.34 7/21 20:15:00 73.89 0.01
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.76 (kBtu/h) 7.49 (kBtu/h) 144.08 186.46 1/21 09:30:00 -31.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.29 (ton) 0.32 (ton) 165.27 180.1 7/21 20:15:00 73.89 0.01
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 5.76 (kBtu/h) 7.48 (kBtu/h) 144.08 186.46 1/21 09:30:00 -31.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.46 (ton) 0.51 (ton) 262.74 290.29 7/21 09:00:00 73.36 0.01
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.69 (kBtu/h) 11.3 (kBtu/h) 216.13 281.81 1/21 09:30:00 -31.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Cooling 0.53 (ton) 0.58 (ton) 300.88 330.55 7/21 20:00:00 74.3 0.01
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN Heating 8.75 (kBtu/h) 11.37 (kBtu/h) 218.24 281.81 1/21 09:30:00 -31.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.49 (ton) 254.27 279.69 7/21 14:00:00 83.66 0.01
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.66 (kBtu/h) 7.36 (kBtu/h) 139.85 182.22 1/21 09:30:00 -31.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.45 (ton) 0.5 (ton) 256.38 281.81 7/21 14:00:00 83.66 0.01
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 5.66 (kBtu/h) 7.36 (kBtu/h) 139.85 182.22 1/21 09:30:00 -31.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.6 (ton) 0.66 (ton) 343.26 377.16 7/21 14:00:00 83.66 0.01
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.6 (kBtu/h) 11.18 (kBtu/h) 214.01 277.57 1/21 09:30:00 -31.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Cooling 0.63 (ton) 0.69 (ton) 358.09 394.11 7/21 19:00:00 76.35 0.01
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN Heating 8.66 (kBtu/h) 11.26 (kBtu/h) 216.13 279.69 1/21 09:30:00 -31.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Cooling 0.89 (ton) 0.98 (ton) 508.53 559.38 7/21 13:45:00 83.43 0.01
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN Heating 8.49 (kBtu/h) 11.04 (kBtu/h) 207.65 269.1 1/21 08:00:00 -31.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Cooling 0.44 (ton) 0.48 (ton) 250.03 275.45 7/21 15:30:00 83.1 0.01
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN Heating 11.71 (kBtu/h) 15.22 (kBtu/h) 286.05 372.92 1/21 09:00:00 -31.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.34 (ton) 0.37 (ton) 192.82 211.89 7/21 20:00:00 74.3 0.01
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 10.69 (kBtu/h) 13.9 (kBtu/h) 260.62 339.02 1/21 09:00:00 -31.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.34 (ton) 0.37 (ton) 192.82 211.89 7/21 14:30:00 83.66 0.01
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 10.69 (kBtu/h) 13.89 (kBtu/h) 260.62 339.02 1/21 09:00:00 -31.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.62 (ton) 0.68 (ton) 351.73 387.76 7/21 09:15:00 74.16 0.01
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 13.53 (kBtu/h) 17.59 (kBtu/h) 330.55 430.13 1/21 09:00:00 -31.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Cooling 0.68 (ton) 0.75 (ton) 385.64 423.78 7/21 17:00:00 81.03 0.01
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN Heating 13.59 (kBtu/h) 17.66 (kBtu/h) 332.66 432.25 1/21 09:00:00 -31.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.69 (ton) 0.76 (ton) 394.11 432.25 7/21 13:45:00 83.43 0.01
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 10.6 (kBtu/h) 13.78 (kBtu/h) 258.5 336.9 1/21 09:00:00 -31.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.69 (ton) 0.76 (ton) 396.23 434.37 7/21 13:45:00 83.43 0.01
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 10.59 (kBtu/h) 13.77 (kBtu/h) 258.5 336.9 1/21 09:00:00 -31.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.82 (ton) 0.9 (ton) 464.03 510.65 7/21 13:45:00 83.43 0.01
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 13.44 (kBtu/h) 17.47 (kBtu/h) 328.43 428.01 1/21 09:00:00 -31.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Cooling 0.82 (ton) 0.9 (ton) 468.27 514.89 7/21 15:45:00 82.81 0.01
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN Heating 13.5 (kBtu/h) 17.55 (kBtu/h) 330.55 430.13 1/21 09:00:00 -31.0 0.0

Zone Equipment Detail


Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Object Sizing Sizing Units Description Value Value Units Count
OS:ZoneHVAC:Baseboard:Convective:Electric
OS:ZoneHVAC:PackagedTerminalAirConditioner - OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O

Air Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:DX:SingleSpeed Autosized Btu/h Rated COP 3.42 COP
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:ConstantVolume Autosized cfm Pressure Rise 2.57 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 68.0 to 68.0 F
(demand)
Thermal Zones Total Floor Area 83,401 ft^2 89
Thermal Zones thermostat ranges for cooling 75.2 to 75.2 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:Uncontrolled 89
(controls)
HVAC Operation Schedule Make-up air unit Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting DifferentialEnthalpy Choice
Demand Controlled Ventilation Status false Bool

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:AirLoopHVAC:OutdoorAirSystem Autosized cfm Minimum Outdoor Air Flow Rate 0.00 cfm
OS:Coil:Cooling:Water Autosized gal/min Plant Loop Chilled Water Loop
OS:Coil:Heating:Electric Autosized Btu/h Efficiency 1.00
OS:Fan:VariableVolume Autosized cfm Pressure Rise 5.85 inH_{2}O
OS:SetpointManager:Scheduled Control Variable - Temperature 55.4 to 55.4 F
(demand)
Thermal Zones Total Floor Area 950 ft^2 1
Thermal Zones thermostat ranges for cooling 75.2 to 95.0 F
Thermal Zones thermostat ranges for heating 64.4 to 71.6 F
Terminal Types Used OS:AirTerminal:SingleDuct:VAV:Reheat 1
(controls)
HVAC Operation Schedule VAV with Reheat Occ Sch
Night Cycle Setting CycleOnAny Choice
Economizer Setting NoEconomizer Choice
Demand Controlled Ventilation Status false Bool

Plant Loops Detail


Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:Chiller:Electric:EIR 15,322.74 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
OS:SetpointManager:Scheduled Control Variable - Temperature 44.6 to 44.6 F
OS:Chiller:Electric:EIR 0.00 Btu/h Reference COP 4.50
OS:Chiller:Electric:EIR (cont) Chiller Source Condenser Water Loop
(demand)
OS:Coil:Cooling:Water Air Loop VAV with Reheat
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 44.60 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:CoolingTower:SingleSpeed - Air Autosized gal/min
OS:CoolingTower:SingleSpeed (cont) - Water Autosized cfm Fan Power at Design Air Flow Rate 174,421.94 W
OS:SetpointManager:Scheduled Control Variable - Temperature 84.2 to 84.2 F
(demand)
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
OS:Chiller:Electric:EIR Plant Loop Chilled Water Loop
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 32.0 to 212.0 F
Design Loop Exit Temperature 84.20 F
Loop Design Temperature Difference 10.80 R

Object Sizing Sizing Units Description Value Value Units Count
(supply)
OS:Pump:ConstantSpeed Autosized gal/min Rated Power Consumption Autosized W
OS:WaterHeater:Mixed 600 gal Heater Thermal Efficiency 1.00 fraction
OS:SetpointManager:Scheduled Control Variable - Temperature 140.0 to 140.0 F
(demand)
OS:WaterUse:Connections Water Use Connections 1
OS:WaterUse:Connections Water Use Connections 2
OS:WaterUse:Connections Water Use Connections 3
OS:WaterUse:Connections Water Use Connections 4
OS:WaterUse:Connections Water Use Connections 5
OS:WaterUse:Connections Water Use Connections 6
OS:WaterUse:Connections Water Use Connections 7
OS:WaterUse:Connections Water Use Connections 8
OS:WaterUse:Connections Water Use Connections 9
OS:WaterUse:Connections Water Use Connections 10
OS:WaterUse:Connections Water Use Connections 11
OS:WaterUse:Connections Water Use Connections 12
OS:WaterUse:Connections Water Use Connections 13
OS:WaterUse:Connections Water Use Connections 14
OS:WaterUse:Connections Water Use Connections 15
OS:WaterUse:Connections Water Use Connections 16
OS:WaterUse:Connections Water Use Connections 17
OS:WaterUse:Connections Water Use Connections 18
OS:WaterUse:Connections Water Use Connections 19
OS:WaterUse:Connections Water Use Connections 20
OS:WaterUse:Connections Water Use Connections 21
OS:WaterUse:Connections Water Use Connections 22
OS:WaterUse:Connections Water Use Connections 23
OS:WaterUse:Connections Water Use Connections 24
OS:WaterUse:Connections Water Use Connections 25
OS:WaterUse:Connections Water Use Connections 26
OS:WaterUse:Connections Water Use Connections 27
OS:WaterUse:Connections Water Use Connections 28
OS:WaterUse:Connections Water Use Connections 29
OS:WaterUse:Connections Water Use Connections 30
OS:WaterUse:Connections Water Use Connections 31
OS:WaterUse:Connections Water Use Connections 32
OS:WaterUse:Connections Water Use Connections 33
OS:WaterUse:Connections Water Use Connections 34
OS:WaterUse:Connections Water Use Connections 35
OS:WaterUse:Connections Water Use Connections 36
OS:WaterUse:Connections Water Use Connections 37
OS:WaterUse:Connections Water Use Connections 38
OS:WaterUse:Connections Water Use Connections 39
OS:WaterUse:Connections Water Use Connections 40
OS:WaterUse:Connections Water Use Connections 41
OS:WaterUse:Connections Water Use Connections 42
OS:WaterUse:Connections Water Use Connections 43
OS:WaterUse:Connections Water Use Connections 44
OS:WaterUse:Connections Water Use Connections 45
OS:WaterUse:Connections Water Use Connections 46
OS:WaterUse:Connections Water Use Connections 47
OS:WaterUse:Connections Water Use Connections 48
OS:WaterUse:Connections Water Use Connections 49
OS:WaterUse:Connections Water Use Connections 50
OS:WaterUse:Connections Water Use Connections 51
OS:WaterUse:Connections Water Use Connections 52
OS:WaterUse:Connections Water Use Connections 53
OS:WaterUse:Connections Water Use Connections 54
OS:WaterUse:Connections Water Use Connections 55
OS:WaterUse:Connections Water Use Connections 56
OS:WaterUse:Connections Water Use Connections 57
OS:WaterUse:Connections Water Use Connections 58
OS:WaterUse:Connections Water Use Connections 59
OS:WaterUse:Connections Water Use Connections 60
OS:WaterUse:Connections Water Use Connections 61
OS:WaterUse:Connections Water Use Connections 62
OS:WaterUse:Connections Water Use Connections 63
OS:WaterUse:Connections Water Use Connections 64
OS:WaterUse:Connections Water Use Connections 65
OS:WaterUse:Connections Water Use Connections 66
OS:WaterUse:Connections Water Use Connections 67
OS:WaterUse:Connections Water Use Connections 68
OS:WaterUse:Connections Water Use Connections 69
OS:WaterUse:Connections Water Use Connections 70
OS:WaterUse:Connections Water Use Connections 71
OS:WaterUse:Connections Water Use Connections 72
OS:WaterUse:Connections Water Use Connections 73
OS:WaterUse:Connections Water Use Connections 74
OS:WaterUse:Connections Water Use Connections 75
OS:WaterUse:Connections Water Use Connections 76
OS:WaterUse:Connections Water Use Connections 77
OS:WaterUse:Connections Water Use Connections 78
OS:WaterUse:Connections Water Use Connections 79
OS:WaterUse:Connections Water Use Connections 80
(controls)
Loop Flow Rate Range Autosized gal/min Minimum Loop Flow Rate 0.0 gal/min
Loop Temperature Range 50.0 to 140.0 F
Design Loop Exit Temperature 140.00 F
Loop Design Temperature Difference 9.00 R

Outdoor Air


Average Number of Occupants Nominal Number of Occupants Zone Volume (ft^3) Avg. Mechanical Ventilation (ach) Min. Mechanical Ventilation (ach) Avg. Infiltration (ach) Min. Infiltration (ach) Avg. Simple Ventilation (ach) Min. Simple Ventilation (ach)
SP-F2 CORRIDOR SYS-1 FLR-7 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.41 0.352 0.013 0.0 0.0 0.0
SP-F2 N1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.456 0.397 0.039 0.0 0.0 0.0
SP-F2 N2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.456 0.397 0.039 0.0 0.0 0.0
SP-F2 NE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.456 0.397 0.064 0.0 0.0 0.0
SP-F2 NW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.397 0.064 0.0 0.0 0.0
SP-F2 S1 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.476 0.398 0.039 0.0 0.0 0.0
SP-F2 S2 APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.476 0.398 0.039 0.0 0.0 0.0
SP-F2 SE APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.474 0.397 0.064 0.0 0.0 0.0
SP-F2 SW APARTMENT SYS-1 FLR-7 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.468 0.397 0.064 0.0 0.0 0.0
SP-F3 CORRIDOR SYS-1 FLR-9 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.411 0.352 0.015 0.0 0.0 0.0
SP-F3 N1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.397 0.046 0.0 0.0 0.0
SP-F3 N2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.458 0.397 0.046 0.0 0.0 0.0
SP-F3 NE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.076 0.0 0.0 0.0
SP-F3 NW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.453 0.397 0.076 0.0 0.0 0.0
SP-F3 S1 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.477 0.398 0.046 0.0 0.0 0.0
SP-F3 S2 APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.477 0.398 0.046 0.0 0.0 0.0
SP-F3 SE APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.472 0.397 0.076 0.0 0.0 0.0
SP-F3 SW APARTMENT SYS-1 FLR-9 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.469 0.397 0.076 0.0 0.0 0.0
SP-F4 CORRIDOR SYS-1 FLR-8 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.411 0.352 0.017 0.0 0.0 0.0
SP-F4 N1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.458 0.397 0.051 0.0 0.0 0.0
SP-F4 N2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.458 0.397 0.051 0.0 0.0 0.0
SP-F4 NE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.085 0.0 0.0 0.0
SP-F4 NW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.397 0.085 0.0 0.0 0.0
SP-F4 S1 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.477 0.398 0.051 0.0 0.0 0.0
SP-F4 S2 APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.477 0.398 0.051 0.0 0.0 0.0
SP-F4 SE APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.471 0.397 0.085 0.0 0.0 0.0
SP-F4 SW APARTMENT SYS-1 FLR-8 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.469 0.397 0.085 0.0 0.0 0.0
SP-F6 CORRIDOR SYS-1 FLR-2 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.411 0.352 0.02 0.0 0.0 0.0
SP-F6 N1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.456 0.397 0.059 0.0 0.0 0.0
SP-F6 N2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.456 0.397 0.059 0.0 0.0 0.0
SP-F6 NE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.456 0.397 0.098 0.0 0.0 0.0
SP-F6 NW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.397 0.098 0.0 0.0 0.0
SP-F6 S1 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.476 0.397 0.059 0.0 0.0 0.0
SP-F6 S2 APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.475 0.397 0.059 0.0 0.0 0.0
SP-F6 SE APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.469 0.397 0.098 0.0 0.0 0.0
SP-F6 SW APARTMENT SYS-1 FLR-2 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.468 0.397 0.098 0.0 0.0 0.0
SP-F7 CORRIDOR SYS-1 FLR-6 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.41 0.352 0.021 0.0 0.0 0.0
SP-F7 N1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.455 0.397 0.063 0.0 0.0 0.0
SP-F7 N2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.455 0.397 0.063 0.0 0.0 0.0
SP-F7 NE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.456 0.397 0.104 0.0 0.0 0.0
SP-F7 NW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.451 0.397 0.104 0.0 0.0 0.0
SP-F7 S1 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.475 0.397 0.063 0.0 0.0 0.0
SP-F7 S2 APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.474 0.397 0.063 0.0 0.0 0.0
SP-F7 SE APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.469 0.397 0.104 0.0 0.0 0.0
SP-F7 SW APARTMENT SYS-1 FLR-6 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.467 0.397 0.104 0.0 0.0 0.0
SP-F8 CORRIDOR SYS-1 FLR-3 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.409 0.352 0.022 0.0 0.0 0.0
SP-F8 N1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.453 0.397 0.066 0.0 0.0 0.0
SP-F8 N2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.453 0.397 0.066 0.0 0.0 0.0
SP-F8 NE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.454 0.397 0.109 0.0 0.0 0.0
SP-F8 NW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.45 0.397 0.109 0.0 0.0 0.0
SP-F8 S1 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.473 0.397 0.066 0.0 0.0 0.0
SP-F8 S2 APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.472 0.397 0.066 0.0 0.0 0.0
SP-F8 SE APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.467 0.397 0.109 0.0 0.0 0.0
SP-F8 SW APARTMENT SYS-1 FLR-3 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.466 0.397 0.109 0.0 0.0 0.0
SP-F9 CORRIDOR SYS-1 FLR-10 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.404 0.351 0.023 0.0 0.0 0.0
SP-F9 N1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.448 0.397 0.068 0.0 0.0 0.0
SP-F9 N2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.448 0.397 0.068 0.0 0.0 0.0
SP-F9 NE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.45 0.397 0.113 0.0 0.0 0.0
SP-F9 NW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.448 0.397 0.113 0.0 0.0 0.0
SP-F9 S1 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.467 0.397 0.069 0.0 0.0 0.0
SP-F9 S2 APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.467 0.397 0.069 0.0 0.0 0.0
SP-F9 SE APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.463 0.397 0.114 0.0 0.0 0.0
SP-F9 SW APARTMENT SYS-1 FLR-10 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.461 0.397 0.114 0.0 0.0 0.0
SP-G CORRIDOR SYS-1 FLR-5 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.406 0.352 0.009 0.0 0.0 0.0
SP-G N1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.447 0.397 0.027 0.0 0.0 0.0
SP-G N2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.447 0.397 0.027 0.0 0.0 0.0
SP-G NE APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.447 0.397 0.045 0.0 0.0 0.0
SP-G NW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.446 0.397 0.045 0.0 0.0 0.0
SP-G S1 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.464 0.398 0.027 0.0 0.0 0.0
SP-G S2 APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.466 0.398 0.027 0.0 0.0 0.0
SP-G SW APARTMENT SYS-1 FLR-5 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.463 0.397 0.045 0.0 0.0 0.0
SP-M CORRIDOR SYS-1 FLR-1 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.411 0.352 0.018 0.0 0.0 0.0
SP-M N1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.056 0.0 0.0 0.0
SP-M N2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.457 0.397 0.056 0.0 0.0 0.0
SP-M NE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.457 0.397 0.092 0.0 0.0 0.0
SP-M NW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.452 0.397 0.092 0.0 0.0 0.0
SP-M S1 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.477 0.397 0.056 0.0 0.0 0.0
SP-M S2 APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.476 0.397 0.056 0.0 0.0 0.0
SP-M SE APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.47 0.397 0.092 0.0 0.0 0.0
SP-M SW APARTMENT SYS-1 FLR-1 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.468 0.397 0.092 0.0 0.0 0.0
SP-OFFICE SYS-6 FLR-5 SCH-A HPLCMT-SOUTH ZN 2.37 4.42 9498 0.358 0.0 0.049 0.0 0.0 0.0
SP-T CORRIDOR SYS-1 FLR-4 SCH-G HPLCMT-EAST ZN 0.53 0.78 8359 0.387 0.35 0.201 0.0 0.0 0.0
SP-T N1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.435 0.396 0.248 0.0 0.0 0.0
SP-T N2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9499 0.434 0.396 0.248 0.0 0.0 0.0
SP-T NE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.441 0.396 0.295 0.0 0.0 0.0
SP-T NW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-NORTH ZN 1.0 1.47 9498 0.441 0.396 0.295 0.0 0.0 0.0
SP-T S1 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.447 0.396 0.248 0.0 0.0 0.0
SP-T S2 APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9499 0.447 0.396 0.248 0.0 0.0 0.0
SP-T SE APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.45 0.396 0.295 0.0 0.0 0.0
SP-T SW APARTMENT SYS-1 FLR-4 SCH-G HPLCMT-SOUTH ZN 1.0 1.47 9498 0.451 0.396 0.295 0.0 0.0 0.0

Cash Flow

No Data to Show for Cash Flow

Site and Source Summary


Total Energy (kBtu) Energy Per Total Building Area (kBtu/ft^2) Energy Per Conditioned Building Area (kBtu/ft^2)
Total Site Energy 4171144.1 49.4 49.4
Net Site Energy 4171144.1 49.4 49.4
Total Source Energy 13210002.1 156.6 156.6
Net Source Energy 13210002.1 156.6 156.6

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613

Schedule Overview


Schedule Type Limits Rules Use Count
Air Velocity Schedule Velocity 0 3
Always On Dimensionless 0 90
CHW Temp Temperature 3 1
Clothing Schedule ClothingInsulation 1 3
CW Temp Temperature 3 1
Make-up air unit Occ Sch Dimensionless 7 2
Makeup-Air Unit Supply Air Temp Temperature 0 1
NECB-A-Electric-Equipment Dimensionless 3 1
NECB-A-Lighting Dimensionless 3 1
NECB-A-Occupancy Dimensionless 3 1
NECB-A-Service Water Heating Dimensionless 3 1
NECB-A-Thermostat Setpoint-Cooling Temperature 3 3
NECB-A-Thermostat Setpoint-Heating Temperature 3 3
NECB-Activity ActivityLevel 0 90
NECB-G-Electric-Equipment Dimensionless 3 89
NECB-G-Lighting Dimensionless 3 89
NECB-G-Occupancy Dimensionless 3 89
NECB-G-Service Water Heating Dimensionless 3 79
NECB-G-Thermostat Setpoint-Cooling Temperature 3 180
NECB-G-Thermostat Setpoint-Heating Temperature 3 180
ON_OFF_ALWAYS_OFF Availability 3 89
Schedule Ruleset 10 0 1
Schedule Ruleset 100 0 1
Schedule Ruleset 101 0 1
Schedule Ruleset 102 0 1
Schedule Ruleset 103 0 1
Schedule Ruleset 104 0 1
Schedule Ruleset 105 0 1
Schedule Ruleset 106 0 1
Schedule Ruleset 107 0 1
Schedule Ruleset 108 0 1
Schedule Ruleset 109 0 1
Schedule Ruleset 11 0 1
Schedule Ruleset 110 0 1
Schedule Ruleset 111 0 1
Schedule Ruleset 112 0 1
Schedule Ruleset 113 0 1
Schedule Ruleset 114 0 1
Schedule Ruleset 115 0 1
Schedule Ruleset 116 0 1
Schedule Ruleset 117 0 1
Schedule Ruleset 118 0 1
Schedule Ruleset 119 0 1
Schedule Ruleset 12 0 1
Schedule Ruleset 120 0 1
Schedule Ruleset 121 0 1
Schedule Ruleset 122 0 1
Schedule Ruleset 123 0 1
Schedule Ruleset 124 0 1
Schedule Ruleset 125 0 1
Schedule Ruleset 126 0 1
Schedule Ruleset 127 0 1
Schedule Ruleset 128 0 1
Schedule Ruleset 129 0 1
Schedule Ruleset 13 0 1
Schedule Ruleset 130 0 1
Schedule Ruleset 131 0 1
Schedule Ruleset 132 0 1
Schedule Ruleset 133 0 1
Schedule Ruleset 134 0 1
Schedule Ruleset 135 0 1
Schedule Ruleset 136 0 1
Schedule Ruleset 137 0 1
Schedule Ruleset 138 0 1
Schedule Ruleset 139 0 1
Schedule Ruleset 14 0 1
Schedule Ruleset 140 0 1
Schedule Ruleset 141 0 1
Schedule Ruleset 142 0 1
Schedule Ruleset 143 0 1
Schedule Ruleset 144 0 1
Schedule Ruleset 145 0 1
Schedule Ruleset 146 0 1
Schedule Ruleset 147 0 1
Schedule Ruleset 148 0 1
Schedule Ruleset 149 0 1
Schedule Ruleset 15 0 1
Schedule Ruleset 150 0 1
Schedule Ruleset 151 0 1
Schedule Ruleset 152 0 1
Schedule Ruleset 153 0 1
Schedule Ruleset 154 0 1
Schedule Ruleset 155 0 1
Schedule Ruleset 156 0 1
Schedule Ruleset 157 0 1
Schedule Ruleset 158 0 1
Schedule Ruleset 159 0 1
Schedule Ruleset 16 0 1
Schedule Ruleset 160 0 1
Schedule Ruleset 161 0 1
Schedule Ruleset 162 0 1
Schedule Ruleset 163 0 1
Schedule Ruleset 164 0 1
Schedule Ruleset 165 0 1
Schedule Ruleset 166 0 1
Schedule Ruleset 167 0 1
Schedule Ruleset 168 0 1
Schedule Ruleset 169 0 1
Schedule Ruleset 17 0 1
Schedule Ruleset 170 0 1
Schedule Ruleset 171 0 1
Schedule Ruleset 172 0 1
Schedule Ruleset 173 0 1
Schedule Ruleset 174 0 1
Schedule Ruleset 175 0 1
Schedule Ruleset 176 0 1
Schedule Ruleset 177 0 1
Schedule Ruleset 178 0 1
Schedule Ruleset 179 0 1
Schedule Ruleset 18 0 1
Schedule Ruleset 180 0 1
Schedule Ruleset 181 0 1
Schedule Ruleset 182 0 1
Schedule Ruleset 183 0 1
Schedule Ruleset 184 0 1
Schedule Ruleset 185 0 1
Schedule Ruleset 186 0 1
Schedule Ruleset 187 0 1
Schedule Ruleset 188 0 1
Schedule Ruleset 189 0 1
Schedule Ruleset 19 0 1
Schedule Ruleset 190 0 1
Schedule Ruleset 191 0 1
Schedule Ruleset 192 0 1
Schedule Ruleset 193 0 1
Schedule Ruleset 194 0 1
Schedule Ruleset 195 0 1
Schedule Ruleset 196 0 1
Schedule Ruleset 197 0 1
Schedule Ruleset 198 0 1
Schedule Ruleset 199 0 1
Schedule Ruleset 20 0 1
Schedule Ruleset 200 0 1
Schedule Ruleset 201 0 1
Schedule Ruleset 202 0 1
Schedule Ruleset 203 0 1
Schedule Ruleset 204 0 1
Schedule Ruleset 205 0 1
Schedule Ruleset 206 0 1
Schedule Ruleset 207 0 1
Schedule Ruleset 208 0 1
Schedule Ruleset 209 0 1
Schedule Ruleset 21 0 1
Schedule Ruleset 210 0 1
Schedule Ruleset 211 0 1
Schedule Ruleset 212 0 1
Schedule Ruleset 213 0 1
Schedule Ruleset 214 0 1
Schedule Ruleset 215 0 1
Schedule Ruleset 216 0 1
Schedule Ruleset 217 0 1
Schedule Ruleset 218 0 1
Schedule Ruleset 219 0 1
Schedule Ruleset 22 0 1
Schedule Ruleset 220 0 1
Schedule Ruleset 221 0 1
Schedule Ruleset 222 0 1
Schedule Ruleset 223 0 1
Schedule Ruleset 224 0 1
Schedule Ruleset 225 0 1
Schedule Ruleset 226 0 1
Schedule Ruleset 227 0 1
Schedule Ruleset 228 0 1
Schedule Ruleset 229 0 1
Schedule Ruleset 23 0 1
Schedule Ruleset 230 0 1
Schedule Ruleset 231 0 1
Schedule Ruleset 232 0 1
Schedule Ruleset 233 0 1
Schedule Ruleset 234 0 1
Schedule Ruleset 235 0 1
Schedule Ruleset 236 0 1
Schedule Ruleset 237 0 1
Schedule Ruleset 238 0 1
Schedule Ruleset 239 0 1
Schedule Ruleset 24 0 1
Schedule Ruleset 240 0 1
Schedule Ruleset 241 0 1
Schedule Ruleset 242 0 1
Schedule Ruleset 25 0 1
Schedule Ruleset 26 0 1
Schedule Ruleset 27 0 1
Schedule Ruleset 28 0 1
Schedule Ruleset 29 0 1
Schedule Ruleset 3 0 1
Schedule Ruleset 30 0 1
Schedule Ruleset 31 0 1
Schedule Ruleset 32 0 1
Schedule Ruleset 33 0 1
Schedule Ruleset 34 0 1
Schedule Ruleset 35 0 1
Schedule Ruleset 36 0 1
Schedule Ruleset 37 0 1
Schedule Ruleset 38 0 1
Schedule Ruleset 39 0 1
Schedule Ruleset 4 0 1
Schedule Ruleset 40 0 1
Schedule Ruleset 41 0 1
Schedule Ruleset 42 0 1
Schedule Ruleset 43 0 1
Schedule Ruleset 44 0 1
Schedule Ruleset 45 0 1
Schedule Ruleset 46 0 1
Schedule Ruleset 47 0 1
Schedule Ruleset 48 0 1
Schedule Ruleset 49 0 1
Schedule Ruleset 5 0 1
Schedule Ruleset 50 0 1
Schedule Ruleset 51 0 1
Schedule Ruleset 52 0 1
Schedule Ruleset 53 0 1
Schedule Ruleset 54 0 1
Schedule Ruleset 55 0 1
Schedule Ruleset 56 0 1
Schedule Ruleset 57 0 1
Schedule Ruleset 58 0 1
Schedule Ruleset 59 0 1
Schedule Ruleset 6 0 1
Schedule Ruleset 60 0 1
Schedule Ruleset 61 0 1
Schedule Ruleset 62 0 1
Schedule Ruleset 63 0 1
Schedule Ruleset 64 0 1
Schedule Ruleset 65 0 1
Schedule Ruleset 66 0 1
Schedule Ruleset 67 0 1
Schedule Ruleset 68 0 1
Schedule Ruleset 69 0 1
Schedule Ruleset 7 0 1
Schedule Ruleset 70 0 1
Schedule Ruleset 71 0 1
Schedule Ruleset 72 0 1
Schedule Ruleset 73 0 1
Schedule Ruleset 74 0 1
Schedule Ruleset 75 0 1
Schedule Ruleset 76 0 1
Schedule Ruleset 77 0 1
Schedule Ruleset 78 0 1
Schedule Ruleset 79 0 1
Schedule Ruleset 8 0 1
Schedule Ruleset 80 0 1
Schedule Ruleset 81 0 1
Schedule Ruleset 82 0 1
Schedule Ruleset 83 0 1
Schedule Ruleset 84 0 1
Schedule Ruleset 85 0 1
Schedule Ruleset 86 0 1
Schedule Ruleset 87 0 1
Schedule Ruleset 88 0 1
Schedule Ruleset 89 0 1
Schedule Ruleset 9 0 1
Schedule Ruleset 90 0 1
Schedule Ruleset 91 0 1
Schedule Ruleset 92 0 1
Schedule Ruleset 93 0 1
Schedule Ruleset 94 0 1
Schedule Ruleset 95 0 1
Schedule Ruleset 96 0 1
Schedule Ruleset 97 0 1
Schedule Ruleset 98 0 1
Schedule Ruleset 99 0 1
Service Water Loop Temp - 140F Temperature 0 2
Supply Air Temp Temperature 0 1
VAV with Reheat Occ Sch Dimensionless 7 2
Water Heater Ambient Temp Schedule - 70F Temperature 0 1
Work Efficiency Schedule Dimensionless 0 3